Instrument Junction Boxes (commonly referred to as JBs) are an integral part of every control and instrumentation installation. They protect electrical connections from the weather, help prevent operators and technicians from suffering accidental electric shocks, and offer a convenient entry into a Contact online >>
Instrument Junction Boxes (commonly referred to as JBs) are an integral part of every control and instrumentation installation. They protect electrical connections from the weather, help prevent operators and technicians from suffering accidental electric shocks, and offer a convenient entry into a circuit for maintenance and fault finding.
In this article we will look at the considerations and options available when specifying a junction box, and also at some of the documentation used by instrument designers and technicians relating to Junction Boxes.
An instrument junction box is an enclosure housing terminals that allows interconnection between field devices (i.e. instruments, switches etc) in the process/production areas, and control or monitoring equipment typically located in the control room.
Typically, numerous field cables of a common system are joined, via the terminal blocks within the JB, to a multicore cable. Examples could be analogue signals to the DCS, switch signals to DCS, analogue signals from DCS, analogue signals to ESD etc.
Like every part of an instrument loop, it is essential that the JB selected is suitable for the required application. Consideration needs to be given to:- Materials of construction,- Suitbility for use in hazardous areas,- Degree of ingress protection,- Type and quantity of terminals to be housed within the JB,- Number of cable entries and their direction,- Earthing,- Requirement for breather or drain plug,- Junction box size and mounting,- Labeling,- Doors.
Junction boxes can be manufactured in a variety of materials including stainless steel, mild steel, glass reinforced polyester, aluminum, polycarbonate and ABS (Acrylonitrile butadiene styrene - a thermoplastic polymer). These are all suitable for a wide range of industrial and OEM applications.
For outdoor areas that are exposed to changing environmental conditions like those encountered in many process and petrochemical plants, and Oil & Gas installations, the use of materials with good corrosion resistance, the ability to tolerate high ambient temperatures and high creep strength, is important. That is why stainless steel is most often selected, with GRP being a popular second choice.
Glass Reinforced Polyester (GRP) has a high resistance to contamination from oils, has excellent mechanical properties (e.g. strength), and offers a long life expectancy.
Junction boxes, certified suitable for use in potentially Hazardous Areas are available from many manufacturers. Common certification standards include the ATEX Standard, and the IEC 60079-series of explosion prevention standards. For JBs, the most common types of protection used are Ex d "flameproof" and Ex e "increased safety". Though it is not uncommon to see Ex"N", or indeed Ex"P". Ex e is often used for junction boxes in intrinsically safe circuits.
For Ex e certified JBs there are two main criteria to consider;- Are the internal components e.g. terminals etc acceptable for use in the JB i.e. only terminals or other components which are specifically allowed for in the JB''s certificate of compliance, and- Will any internal components, or wiring, be hotter than the temperature classification of the JB allows.
In all Ex certified enclosures it is important that an earth facility is provided. For metallic enclosures the earth facility must earth the enclosure body and can be provided by earth terminals connected to the body through the terminal mounting rail and/or by means of an internal/external earth stud.
A major secondary form of protection for the internals of a JB is its IP rating. Moisture or dust, if allowed to come into contact with the JB internals, could lead to either sparking or physical breakdown of the components and interfere with the explosion protection method being used. It is for this reason that IP56 is usually considered the minimum rating that should be used for junction boxes, especially if they are located outside.
If the junction box could be subject to deluge conditions, as is common in many offshore oil and gas platforms, then greater ingress protection will be required. For deluge service consider specifying that the equipment should meet the requirements of Shell DTS:01.
As already mentioned above, only terminals which are specifically allowed for in the JB''s certificate of compliance should be used. Most reputable manufacturers offer junction boxes that can accept terminals from the a wide range of brands e.g. Weidmüller, Pheonix Contact, ABB, Legrand, Rockwell automation etc.
A removable "gear plate" (or component mounting plate) is usually provided. DIN standard terminal rails can be fixed to the gear plate, before the plate is mounted in the box. This makes for easy and quicker assembly of the box.
Cable glands should be selected according to the cable type, screen or armour earthing requirements and the IP rating required. For junction boxes used in hazardous areas the gland must must have the same criteria as the enclosure to which they are connected.
Ex e junction boxes are usually supplied with gland plates which are drilled to accept cable glands which allow cable entry. The gland plate is bolted to the JB and supplied with a gasket to maintian IP rating. It is important to always allow enough clearance around multiple gland entries to allow for fixing nuts etc. Note, the choice of gland, and by implication its size, may limit the number of entries possible in any given gland plate.
There is no hard and fast rule about where cables should enter a box. It is often the case however that incoming cables enter the box from the side, and the multicore exits from the bottom of the box. Different configurations of cable entry may impact on the size of box required.
As mentioned above, all Ex certified enclosures must be provided with an earth facility. These are usually an M6 internal to M10 external SS316L earth stud. It is common for Earth studs to be welded to the enclosure wall to maintain integrity of the IP rating.
The Breather part of a Breather Drain plug provides pressure compensation between the inside of the junction box and the external atmosphere. This minimises moisture build up caused by temperature fluctuations and humid environments.The Drain part of the plug allows any condensed water present within the junction box to be drained before it accumulates and causes problems.
If fitted, and it is good practice to fit these on JBs mounted externally, breather drains must have the same Hazardous Area certification and IP rating as the junction box to which they are fitted.
About Ex e box diagram
As the photovoltaic (PV) industry continues to evolve, advancements in Ex e box diagram have become critical to optimizing the utilization of renewable energy sources. From innovative battery technologies to intelligent energy management systems, these solutions are transforming the way we store and distribute solar-generated electricity.
When you're looking for the latest and most efficient Ex e box diagram for your PV project, our website offers a comprehensive selection of cutting-edge products designed to meet your specific requirements. Whether you're a renewable energy developer, utility company, or commercial enterprise looking to reduce your carbon footprint, we have the solutions to help you harness the full potential of solar energy.
By interacting with our online customer service, you'll gain a deep understanding of the various Ex e box diagram featured in our extensive catalog, such as high-efficiency storage batteries and intelligent energy management systems, and how they work together to provide a stable and reliable power supply for your PV projects.